首页> 美国政府科技报告 >Comparisons of NBS/Harvard VI Simulations and Full-Scale, Multi-Room Fire Test Data
【24h】

Comparisons of NBS/Harvard VI Simulations and Full-Scale, Multi-Room Fire Test Data

机译:NBs / Harvard VI模拟与全尺寸,多房间火灾测试数据的比较

获取原文

摘要

The NBS/Harvard VI multiroom fire model computer code was used to simulate results of previously reported full-scale, multi-room fire experiments. The tests and simulations involved: four different compartment configurations made up of two or three rooms connected by open doorways, four different fire types generated by a methane burner located in the room identified as the burn room and up to four different doorway openings between the burn room and the adjacent space. A total of nineteen different tests were carried out and simulated. Comparisons between simulated and measured parameters of the fire-generated environments are reviewed. While the computer code is generally found to provide excellent simulations for the entire range of tests, several areas in modeling detail are identified as requiring clarification, research, and further improvement. The improvements should be incorporated in future versions of the NBS/Harvard Multi-Room Fire Model.