首页> 美国政府科技报告 >Characterization of PCB (Polychlorinated Biphenyl) Transformer/Capacitor Fluids and Correlation with PCDDs (Polychlorinated Dibenzo-p-dioxins) and PCDFs (Polychlorinated Dibenzofurans) in Soot
【24h】

Characterization of PCB (Polychlorinated Biphenyl) Transformer/Capacitor Fluids and Correlation with PCDDs (Polychlorinated Dibenzo-p-dioxins) and PCDFs (Polychlorinated Dibenzofurans) in Soot

机译:pCB(多氯联苯)变压器/电容器流体的特性及其与pCDD(多氯二苯并对二恶英)和pCDF(多氯二苯并呋喃)在烟尘中的相关性

获取原文

摘要

Dielectric fluids in transformers and capacitors often contain polychlorinated biphenyls (PCBs) or chlorobenzenes. These substances may generate polychlorinated dibenzofurans (PCDFs) and polychlorinated dibenzo-p-dioxins (PCDDs) under certain conditions of combustion/pyrolysis. When electrical equipment containing these fluids is involved in an accidental fire, the resulting smoke, soot, and residues may be contaminated with PCDDs, PCDFs, and other toxic chlorinated hydrocarbons. The report contains a review of several laboratory studies investigating the sources of PCDDs and PCDFs as well as the conditions under which they are formed. In addition, some data from sites of actual fire incidents are available and are discussed. Chlorobenzenes and PCBs do not form PCDDs and PCDFs when heated in the absence of oxygen. During fires the dielectric fluid of transformers or capacitors may be leaked or vented from ruptured casings. With exposure to oxygen, PCBs can produce PCDFs and chlorobenzenes can produce PCDDs.

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号