While simultaneously contacting an injection molding machine which was grounded and a grinding machine with a ground fault, a set up man was electrocuted. The man was employed by a plastics manufacturing company making components for other companies. At the time of the accident, an injection molding machine was producing defective parts. The victim opened the door of the machine to remove and examine one of the products. As he closed the door with one hand, he supported himself with the other by holding the metal handle of a nearby portable grinding machine. Apparently an energized wire to a safety interlock was contacting the metal case of the switch, energizing the metal case of the grinder at 270 volts. No one on the scene was trained in cardiopulmonary resuscitation and it was 16 minutes before emergency help arrived on the scene. While there were no electrical burns on the victim's body, the medical examiner ruled the cause of death to be electrocution as there was no history of heart disease and because a coworker received an electrical shock while attempting to assist the victim.