摘要

Biofouling surveillance and control techniques are evaluated for their applicability to sediment and corrosion fouling and suggestions are given to improve their effectiveness. Alternate techniques to better detect and control sedimentation and corrosion are also evaluated. Environmental conditions that allow biofouling, sedimentation, and corrosion to occur are summarized. A correlation between sediment and corrosion is identified and the causes are described. Environmental regulations, especially those in the Clean Water Act of 1977, are reviewed to identify those that may limit or prevent the use of surveillance and control techniques described in the report. Flow velocity is the major design factor that determines whether or not biofouling, sedimentation, and corrosion will occur. Monitoring flow conditions can provide early warning of conditions that will allow fouling to occur. Visual inspection is the most common and most effective technique for identifying the cause and extent of fouling in the open-cycle water system. Frequent, high-velocity flushing of cooling loops may effectively remove sediment and reduce under-sediment corrosion.