首页> 美国政府科技报告 >Effect of foundation flexibility on the vibrational stability of the National Ignition Facility optical system support structures
【24h】

Effect of foundation flexibility on the vibrational stability of the National Ignition Facility optical system support structures

机译:地基柔性对国家点火装置光学系统支撑结构振动稳定性的影响

获取原文

摘要

Alignment requirements for the National Ignition Facility (NIF) optical components will require a number of support structures which minimize the system displacements and deformations. The stringent design requirements for this facility will result in a system in which vibrations due to ambient environmental loads (e.g. foundation motion due to typical traffic loads, microseisms or nearby equipment) will have a significant, and perhaps predominant, influence on the design of the supporting structures. In the work described in this report, parametric studies were performed in order to understand the potential contributions of soil-structure-interaction (SSI) to optical system displacements. Time domain finite element analyses were employed to quantify the effect of wave scattering by the mat foundation and the effects of inertial SSI due to the rocking of the massive shear wall support structures. A simplified procedure is recommended for accounting for SSI effects in the design of the special equipment structures. The simplified approach consists of applying a scale factor to displacements obtained from fixed base analyses to approximately account for the effects of soil-structure interaction and variable support input motion.