首页> 美国政府科技报告 >LEAKAGE OF WATER FROM GASKETED JOINTS PROPOSED FOR THE HWCTR - PART II AND PUMP MECHANICAL SEAL VAPOR LEAKAGE
【24h】

LEAKAGE OF WATER FROM GASKETED JOINTS PROPOSED FOR THE HWCTR - PART II AND PUMP MECHANICAL SEAL VAPOR LEAKAGE

机译:从HWCTR建议的垫片接头漏水 - 第二部分和泵机械密封气体泄漏

获取原文

摘要

The average leakage rate was less than 0.3 pound per year per linear inch of gasket when mockups of typical joints proposed for the reactor vessel and the isolated coolant loops of the HWCTR were subjected to temperature and pressure cycling. The joints, which were exposed to deionized light water, were cycled about 100 times from 70℃ and atmospheric pressure to 250℃ and pressures of 1500 psig for the vessel joints and 750 psig for the joints designed for the isolated coolant loops.nThe average leakage of water vapor from a pump mechanical seal was less than 1.4- lb/yr during a five-month period. The pump circulated deionized water at 260℃ and 850 psig.

著录项

  • 作者

    Frederick C. Apple;

  • 作者单位
  • 年度 1961
  • 页码 1-28
  • 总页数 28
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 工业技术;
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号