首页> 美国政府科技报告 >ERRORS IN MEASUREMENTS OF BUILDING LEAKAGE DUE TO DYNAMIC TEMPERATURE EFFECTS
【24h】

ERRORS IN MEASUREMENTS OF BUILDING LEAKAGE DUE TO DYNAMIC TEMPERATURE EFFECTS

机译:由动态温度效应引起的建筑物泄漏测量误差

获取原文

摘要

This report analyzes sources of errors in determining leakage rates of a containment structure, when a reference vessel method is used. It is shown that the most serious errors do not arise from lack of precision in measuring absolute temperatures and pressures; rather, the largest errors are shown to be due to a combination of a temperature lag between reference vessel and containment structure, and from temperature fluctuations during the testing period.