首页> 美国政府科技报告 >DEMONSTRATION OF ADIABATIC COOLIWG TO IMPROVE THE PERFORMANCE OF AIR-COOLED HEAT EXCHANGERS
【24h】

DEMONSTRATION OF ADIABATIC COOLIWG TO IMPROVE THE PERFORMANCE OF AIR-COOLED HEAT EXCHANGERS

机译:绝热冷却的改进,以提高空气冷却换热器的性能

获取原文

摘要

A demonstration of improved heat exchanger performance by adiabatically cooling the inlet air to an air-cooled heat exchanger was performed on a condenser that had a design heat rejection rate of 58 million Btu/hr. Pneumatic nozzles ware used to inject atomized water into the inlet air stream. Mean droplet diameters ranged from 16 to 28 microns for all of the tests. Results of these experiments comparing conventional and adiabatic cooling showed that adiabatic cooling does improve heat transfer performance in accordance with expectations.

著录项

  • 作者

    Alan M. Rubin;

  • 作者单位
  • 年度 1975
  • 页码 1-40
  • 总页数 40
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 工业技术;
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号