Scale Formation in Deluged Dry Cooling Systems

机译:在干燥的冷却系统中形成水垢

获取原文

摘要

Deluging of air-cooled heat exchangers with water during warm periods holds the promise of increasing heat rejection capability and reducing the cost of dry cooling. One of the principal uncertainties in the use of the deluge concept is the tendency toward deposition of solids from the delugate. Small amounts of calcium carbonate scale may significantly reduce the cooling efficiency of a deluged system by reducing the heat transfer coefficient and interfering with delugate flow. Thus the question of delugate water quality is of major importance in evaluating scale formation and its effect on heat transfer in the deluged dry cooling system. The paper discusses, in relation to the deluged dry cooling system, the importance of scale prevention, the theory of scale formation and application of this theory to the deluged system, the problems of delugate evaporation, and delugate treatment required to prevent scaling. (ERA citation 01:025696)