Overcurrent Protection for the TFTR Neutral Beam Sources During Spark down

机译:火花下降期间TFTR中性束源的过流保护

获取原文

摘要

The accelerating grid of a neutral beam source (NBS) of the Tokamak Fusion Test Reactor (TFTR) operates at 120 kV and 65 A. The capacitance to ground between the switch tube (ST) and the NBS is C sub 1 approx. 5 nF (approx. 36 J). The arc and filament power supplies for the NBS float at 120 kV and have a capacitance to ground of C sub 2 approx. 2 nF (approx. 14 J). When the NBS sparks to ground, C sub 2 begins to discharge immediately. The ST impedance limits the fault current from the high voltage (HV) power supply to approx. 100 A until it disconnects the power source < 2 mu s after spark down. In case the ST fails, a crowbar removes the power source approx. 4 mu s after spark down and C sub 1 begins to discharge. During spark down, fault currents are limited with a saturated time-delay transformer (STDT) connected between the ST and the NBS and with a snubber, which is in the arc and filament power leads, in connection with a spark gap. Alternatively, STDT's can be used for the HV and for the arc and filament power leads. This paper presents design details and experimental results of the overcurrent protection circuits. (ERA citation 05:017225)