首页> 美国政府科技报告 >Deposition and Corrosion Phenomena on Aluminum Surfaces Under Deluged Dry Cooling-Tower Conditions
【24h】

Deposition and Corrosion Phenomena on Aluminum Surfaces Under Deluged Dry Cooling-Tower Conditions

机译:干燥冷却塔条件下铝表面沉积与腐蚀现象

获取原文

摘要

Deposition and corrosion on aluminum heat exchanger surfaces resulting from deluge in wet/dry cooling towers is simulated in a laboratory Corrosion/Deposition Loop (CDL). Heat exchanger deposition buildup was found to be linearly dependent on concentration factor and number of wet/dry cycles. Deionized water rinsing after deluge reduced rate of deposition.nLaboratory data obtained from CDL relates directly to operation of the Advanced Concepts Test (ACT) demonstration cooling tower. Technology transferable to ACT shows that deposition from supersaturated solution can be effectively controlled by attention to water chemistry, pH, water conditioning, and good heat transfer design. The additional mechanism of deposition by water film evaporation is effectively managed by soft water rinsing and uniform surface wetting.