首页> 美国政府科技报告 >River Gardens Intermediate-Care Facility Water-to-Air Heating and Air-Conditioning Demonstration Project. Final Report
【24h】

River Gardens Intermediate-Care Facility Water-to-Air Heating and Air-Conditioning Demonstration Project. Final Report

机译:河流花园中级护理设施水 - 空气加热和空调示范项目。总结报告

获取原文

摘要

An integrated system of heat pumps is used to reject heat into or extract heat from circulating water from a shallow well adjacent to the river to demonstrate the efficiency and fuel cost savings of water-to-air heat pumps, without the expense of drilling a deep well. Water is returned unpolluted to the Guadalupe River and is circulated through a five-building complex at River Gardens Intermediate Care Facility for the Mentally Retarded in New Braunfels, Texas. The water is used as a heat source or sink for 122 heat pumps providing space heating and cooling, and for refrigeration and freezer units. The system was not installed as designed, which resulted in water pumping loads being higher than the original design. Electrical consumption for pumping water represented 36 to 37% of system electrical consumption. Without the water pumping load, the water-to-air system was an average of 25% more efficient in heating than a comparable air-to-air unit with resistance heating. With water pumping load included, the installed system averaged 17% less efficient in cooling and 19% more efficient in heating than the comparable unit. (ERA citation 08:036145)