首页> 美国政府科技报告 >Summary of Efficiency Testing of Standard and High-Capacity High-Efficiency Particulate Air Filters Subjected to Simulated Tornado Depressurization and Explosive Shock Waves.
【24h】

Summary of Efficiency Testing of Standard and High-Capacity High-Efficiency Particulate Air Filters Subjected to Simulated Tornado Depressurization and Explosive Shock Waves.

机译:模拟龙卷风减压和爆炸冲击波对标准和高容量高效微粒空气过滤器进行效率测试的总结。

获取原文

摘要

Pressure transients in nuclear facility air cleaning systems can originate from natural phenomena such as tornadoes or from accident-induced explosive blast waves. This study was concerned with the effective efficiency of high-efficiency particulate air (HEPA) filters during pressure surges resulting from simulated tornado and explosion transients. The primary objective of the study was to examine filter efficiencies at pressure levels below the point of structural failure. Both standard and high-capacity 0.61-m by 0.61-m HEPA filters were evaluated, as were several 0.2-m by 0.2-m HEPA filters. For a particular manufacturer, the material release when subjected to tornado transients is the same (per unit area) for both the 0.2-m by 0.2-m and the 0.61-m by 0.61-m filters.