首页> 美国政府科技报告 >Emergency AC Power Systems Operating Experience at US Nuclear Power Plants, 1976 Through 1983
【24h】

Emergency AC Power Systems Operating Experience at US Nuclear Power Plants, 1976 Through 1983

机译:美国核电站应急交流电源系统运行经验,1976年至1983年

获取原文

摘要

Success and failure data of test and emergency starts of emergency ac power sources (diesel generators) at US nuclear power plants were collected and evaluated to estimate diesel generator reliability parameters. A regression analysis of the estimates of the probability of failure to start based on surveillance test data from 1976 through 1983 indicates that the probability of failure to start has been decreasing. However, the reliability of diesel generator performance during losses of off-site power for 1981 through 1983 was less than expected based on the test data estimates. The failures that occurred during losses of off-site power were reviewed to determine why the calculated failure to start was greater than expected, and possible explanations for this high value are presented. The subsystems involved in diesel generator subsystem failures were categorized to determine whether there were any dominant failure modes. The results indicate that further significant improvement in diesel generator reliability will require improvement of many subsystems. (ERA citation 11:007221)

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号