首页> 美国政府科技报告 >Temperature History for Canistered Fuel Lag Storage Areas During the Loss of Cooling Air at the Receiving and Handling Building of the MRS Facility
【24h】

Temperature History for Canistered Fuel Lag Storage Areas During the Loss of Cooling Air at the Receiving and Handling Building of the MRS Facility

机译:mRs设施的接收和处理大楼冷却空气损失期间的燃料滞后储存区域的温度历史

获取原文

摘要

The Pacific Northwest Laboratory has analyzed the temperature history at a canistered fuel lag storage area during a postulated failure of the cooling system. A two-dimensional analysis was performed using the GE2D computer code, which accounts for thermal radiation, conduction, and convective heat transfer. The results indicate that the system may not reach a steady-state condition because heat transfer through the top and the bottom of the system is not enough to remove the energy generated in the canistered fuel. Although limits for abnormal operation have not been set, the temperatures do not reach limiting conditions for normal operation for 32 hours, which should be enough time to repair the cooling system. (ERA citation 11:029302)