首页> 美国政府科技报告 >Effects of Steep-Front, Short-Duration Impulses on Power Distribution Components.
【24h】

Effects of Steep-Front, Short-Duration Impulses on Power Distribution Components.

机译:陡前,短时脉冲对配电元件的影响。

获取原文

摘要

A line type pulser has been developed to test the effects of steep-front, short duration (SFSD) pulses on distribution components. Risetime is 50-100 ns, and pulse duration is on the order of 300 ns. Terminators often shattered or punctured rather than flashing over. Insulator flashover voltage is approximately 1.5 times CFO for standard lightning impulses. Arresters exhibit an inductive character, with SFSD peak voltage at 10 kA approximately 4--5 times the 8 x 20 microsecond 10 kA discharge voltage. Polyethylene insulated cable has a characteristic degradation in which failure voltage decreases with number of SFSD pulses. 7 refs., 12 figs., 2 tabs.