首页> 美国政府科技报告 >Study of the utility of heat collectors in reducing the response time of automatic fire sprinklers located in production modules of Building 707
【24h】

Study of the utility of heat collectors in reducing the response time of automatic fire sprinklers located in production modules of Building 707

机译:研究集热器在减少位于707号楼生产模块中的自动消防喷淋头的响应时间的效用

获取原文

摘要

Several of the ten production Modules in Building 707 at the Department of Energy Rocky Flats Plant recently underwent an alteration which can adversely affect the performance of the installed automatic fire sprinkler systems. The Modules have an approximate floor to ceiling height of 17.5 ft. The alterations involved removing the drop ceilings in the Modules which had been at a height of 12 ft above the floor. The sprinkler systems were originally installed with the sprinkler heads located below the drop ceiling in accordance with the nationally recognized NFPA 13, Standard for the Installation of Automatic Sprinkler Systems. The ceiling removal affects the sprinkler's response time and also violates NFPA 13. The scope of this study included evaluation of the feasibility of utilizing heat collectors to reduce the delays in sprinkler response created by the removal of the drop ceilings. The study also includes evaluation of substituting quick response sprinklers for the standard sprinklers currently in place, in combination with a heat collector.