首页> 美国政府科技报告 >Impact of desiccant degradation on desiccant cooling system performance.
【24h】

Impact of desiccant degradation on desiccant cooling system performance.

机译:干燥剂降解对干燥剂冷却系统性能的影响。

获取原文

摘要

The performance of open-cycle desiccant cooling systems depends on several factors, some of which can change beyond manufacturers' specifications. For example, the desiccant sorption process may degrade with time on exposure to airborne contaminants and thermal cycling. Desiccant degradation can reduce the performance of a dehumidifier and thus the performance of desiccant cooling systems. Using computer simulations and recent experimental data on silica gel, the impact of degradation was evaluated. Hypothetical degradations of desiccants with Type 1 moderate isotherms were also simulated. Depending on the degree and type of desiccant degradation, the decrease in thermal coefficient of performance (COP) and cooling capacity of the system was 10% to 35%. The 35% loss in system performance occurs when desiccant degradation is considered worst case. The simulations showed that the COP, and to a lesser degree the cooling capacity of these degraded systems, could be improved by increasing the rotational speed of the dehumidifier. It is shown that easy engineering solutions might be available for some types of degradations. 9 refs., 6 figs., 1 tab. (ERA citation 16:000841)