首页> 美国政府科技报告 >Open cycle heat pump development for local resource use. Phase 2, District heating case study analysis: Final report, September 13, 1988-April 10, 1990.
【24h】

Open cycle heat pump development for local resource use. Phase 2, District heating case study analysis: Final report, September 13, 1988-April 10, 1990.

机译:开放循环热泵开发用于本地资源使用。第二阶段,区域供热案例研究分析:最终报告,1988年9月13日 - 1990年4月10日。

获取原文

摘要

District heating (DH) systems provide thermal energy to their customers in the form of hot water or steam. These systems can use one or more types of heat sources to meet the thermal load, including boilers, cogeneration systems, or low-grade heat sources in conjunction with a heat pump. Most large-scale heat pumps operate using the closed-cycle concept and usually use a chlorinated fluorocarbon (CFC) as the working fluid. An alternative to this approach is the quasi open-cycle heat pump, which was first studied in a Phase 1 report entitled ''Open-Cycle Heat Pump Development for Local Resource Use,'' DOE/CE/26563-5. The quasi open-cycle (QOC) heat pump actually uses the district heating transport medium as its working fluid. This document is the Final Report prepared as a part of Task 6 of Open-Cycle Heat Pump Development for Local Resource Use, Phase 2 District Heating Case Study Analysis. The objective of this study contract was to assess the application of the QOC heat pump in an actual case study. 43 figs., 11 tabs.