首页> 美国政府科技报告 >Seismic evaluation of a cooling water reservoir facility including fluid-structure and soil-structure interaction effects
【24h】

Seismic evaluation of a cooling water reservoir facility including fluid-structure and soil-structure interaction effects

机译:冷却水库设施的抗震评估,包括流体结构和土 - 结构相互作用效应

获取原文

摘要

Seismic analyses and structural evaluations were performed for a cooling water reservoir of a nuclear reactor facility. The horizontal input seismic motion was the NRC Reg. Guide 1.60 spectrum shape anchored at 0.20 g zero period acceleration. Vertical input was taken as two-thirds of the horizontal input. Soil structure interaction and hydrodynamic effects were addressed in the seismic analyses. Uncertainties in the soil properties were accounted for by considering three soil profiles. Two 2-dimensional SSI models and a 3-dimensional static model, representing different areas of the reservoir structures were developed and analyzed to obtain seismic forces and moments, and accelerations at various locations. The results indicated that both hydrodynamic and soil-structure interaction effects are significant contributors to the seismic responses of the water-retaining walls of the reservoir.