A DS-416 low voltage air circuit breaker manufactured by Westinghouse was mechanically cycled to identify age-related degradation in the various breaker subcomponents, specifically the power-operated mechanism. This accelerated aging test was performed on one breaker unit for over 36,000 cycles. Three separate pole shafts, one with a 60-degree weld, one with a 120-degree weld, and one with a 180-degree weld in the third pole lever were used to characterize cracking in the welds. In addition, during the testing three different operating mechanisms and several other parts were replaced as they became inoperable. Among the seven welds on the pole shaft, (number sign)1 and (number sign)3 were found to be critical ones whose fracture can result in misalignment of the pole levers. This can lead to problems with the operating mechanism, including the burning of coils, excessive wear in certain parts, and overstressed linkages. Furthermore, the limiting service life of a number of subcomponents of the power-operated mechanism, including the operating mechanism itself, were assessed. Based on these findings, suggestions are provided to alleviate the age-related degradation that could occur as a result of normal closing and opening of the breaker contacts during its service life. Also, cause and effect analyses of various age-related degradation in various breaker parts are discussed.