首页> 美国政府科技报告 >Pallet fire test for steel drum storage on wooden pallets.
【24h】

Pallet fire test for steel drum storage on wooden pallets.

机译:木制托盘上钢桶存储的托盘防火测试。

获取原文

摘要

A fire test was conducted by the Martin Marietta PORTS Fire Protection Engineering Department on October 3, 1991. This test was designed and set up to simulate a proposed storage configuration. The array consisted of 55-gallon steel drums, filled with noncombustible waste material, placed on wooden pallets stacked three tiers high. Results from the test served as the basis for determining the fire protection requirements for this type of storage. Data acquired from the test indicated that relatively high temperatures were obtained from the ignition source. These readings, taken during short durations throughout the test, were recorded from digital readouts connected to individual thermocouples. The test demonstrated that the wooden pallets did not significantly ignite and basically self-extinguished once the ignition source was consumed. Based upon these findings, storage of this type may be placed in the high bay (70 foot ceilings) sprinklered areas. This is providing that good housekeeping is implemented, large ignition sources are not allowed to be stored or parked in the area, and flammable and combustible liquids and solids are not permitted within the storage zones. The area shall also be designated as a (open quotes)NO SMOKING(close quotes) area.