首页> 美国政府科技报告 >High Expansion Foam Extinguishment of Machinery Space Fires.
【24h】

High Expansion Foam Extinguishment of Machinery Space Fires.

机译:高膨胀泡沫灭火机械空间火灾。

获取原文

摘要

This report details the fire research conducted on board the M/V RHODE ISLAND during the period 10 December 1974 through 17 December 1974. The tests were designed to determine the effects of fill rate, preburn and free venting area on the effectiveness of high expansion foam when used to extinguish machinery space fires. Systems design and agent characteristics were varied in order to determine the optimum and minimum parameters of fire extinguishment. It was shown that high expansion foam could extinguish the fires when applied at a rate of 7 to 9 cubic feet of foam (400-465:1 expansion ratio) per minute per square foot of fire area.

著录项

相似文献