首页> 外文期刊>Physica, C. Superconductivity and its applications >Experimental study on superconducting fault current limiting transformer for fault current suppression and system stability improvement
【24h】

Experimental study on superconducting fault current limiting transformer for fault current suppression and system stability improvement

机译:超导故障限流变压器抑制故障电流及提高系统稳定性的实验研究

获取原文
获取原文并翻译 | 示例

摘要

We have been developing a superconducting fault current limiting transformer (SFCLT) with 3-phase, 500/275 kV, 625 MVA and optimized the main parameters by EMTP simulation. In this paper, we designed and fabricated an experimental scale-down model of SFCLT with 3-phase, 275/105 V, 6.25 kVA, using NbTi superconducting wire. We introduced the experimental model SFCLT into a transient network analyzer consisted of synchronous generators, transformers, transmission lines, circuit breakers and an infinite bus. It was revealed that experimental model had effective function-parameters as was simulated and experimental results clarified the effectiveness of SFCLT having both functions of the fault current suppression and the system stability improvement in a future superconducting power system. (C) 2002 Elsevier Science B.V. All rights reserved. [References: 3]
机译:我们一直在开发三相500/275 kV,625 MVA的超导故障限流变压器(SFCLT),并通过EMTP仿真优化了主要参数。在本文中,我们使用NbTi超导线设计并制造了三相275/105 V,6.25 kVA的SFCLT实验缩小模型。我们将实验模型SFCLT引入到由同步发电机,变压器,传输线,断路器和无限总线组成的瞬态网络分析仪中。结果表明,实验模型具有仿真的有效功能参数,实验结果证明了具有故障电流抑制功能和系统稳定性提高功能的SFCLT在未来的超导电力系统中的有效性。 (C)2002 Elsevier Science B.V.保留所有权利。 [参考:3]

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号