首页> 外文期刊>Steel & Composite Structures: An International Journal >Carbonation depth in 57 years old concrete structures
【24h】

Carbonation depth in 57 years old concrete structures

机译:57年老混凝土结构的碳化深度

获取原文
获取原文并翻译 | 示例
           

摘要

Carbonation depth was verified in 40 points of two 57 years old concrete viaducts. Field testing (phenolphthalein spraying) was performed on the structures. Data obtained were statistically analyzed by the Kolmogrov-Smirnov's test, one-way analysis of variance (ANOVA's test), and Fisher's method. The results revealed significant differences between maximum carbonation depths of different elements of the same concrete structure. Significant differences were also found in the carbonation of different concrete structures inserted in the same macroclimate. Microclimatic factors such as temperature and local humidity, sunshine, wind, wetting and drying cycles, among others, may have been responsible by the behavior of carbonation in concrete.
机译:在两个57年历史的混凝土高架桥中的40个点处验证了碳化深度。在结构上进行了现场测试(酚酞喷涂)。通过Kolmogrov-Smirnov检验,方差单向分析(ANOVA检验)和Fisher方法对获得的数据进行统计分析。结果表明,同一混凝土结构的不同元素的最大碳化深度之间存在显着差异。在插入同一大气候的不同混凝土结构的碳化过程中,也发现了显着差异。温度和局部湿度,日照,风,湿润和干燥周期等微气候因素可能与混凝土碳化的行为有关。