首页> 外文期刊>Measurement Science & Technology >Measurement of electrical polar symmetry in turbogenerator rotors
【24h】

Measurement of electrical polar symmetry in turbogenerator rotors

机译:汽轮发电机转子的电极对称性测量

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

This paper presents a measurement technique and an analysis of the electrical polar symmetry in turbogenerator rotors using the so-called recurrent pulse comparison with the injection of charge as the excitation source. The polar symmetry should be measured because it provides information that allows electrical insulation failures in the rotor winding to be detected. A simple electrical model for the rotor is introduced, and the technique for comparing the recurrent pulses is analysed in detail. The particular measurement instrumentation and the analysis of the results obtained in the time and frequency domains, including their relation to the rotor failures, are also described.
机译:本文介绍了一种测量技术和涡轮发电机转子中电极对称性的分析,该方法使用所谓的循环脉冲比较,并以电荷注入作为激励源。应该测量极性对称性,因为它提供了可以检测出转子绕组中的电绝缘故障的信息。介绍了一种简单的转子电气模型,并详细分析了比较循环脉冲的技术。还描述了特定的测量仪器以及在时域和频域中获得的结果的分析,包括它们与转子故障的关系。