The importance of the dynamic response of guyed towers for transmission lines (TLs) under wind loading is evaluated in this article. The objective is to verify if the simplified static-equivalent approach provided in the current TL codes is sufficient for this type of flexible tower. As a comparison, transient dynamic (TD) analyses were performed. Two different guyed tower configurations were investigated: (i) the direct current (DC) line and (ii) the alternating current (AC) line. Loading cases considering bare and iced TL structures were studied. It was found that, depending on the guyed tower configuration and the loading case, the static-equivalent approach may underestimate the possible dynamic response. In addition, a simplified method that allows a better prediction of the dynamic effects is proposed.
机译:本文评估了风荷载下拉线塔对输电线路(TL)的动态响应的重要性。目的是验证当前TL代码中提供的简化的静态等效方法对于这种类型的柔性塔架是否足够。作为比较,进行了瞬态动态(TD)分析。研究了两种不同的拉杆塔配置:(i)直流(DC)线和(ii)交流(AC)线。研究了考虑裸露和结冰的TL结构的加载情况。已经发现,取决于拉线塔的配置和加载情况,静当量方法可能会低估可能的动态响应。此外,提出了一种简化的方法,可以更好地预测动态效果。