首页> 外文期刊>Experimental Thermal and Fluid Science: International Journal of Experimental Heat Transfer, Thermodynamics, and Fluid Mechanics >Experiments on elliptic sections in one- and two-row arrangements of plate fin and tube heat exchangers
【24h】

Experiments on elliptic sections in one- and two-row arrangements of plate fin and tube heat exchangers

机译:板翅片和管式换热器一排和两排椭圆形截面的实验

获取原文
获取原文并翻译 | 示例
       

摘要

In order to determine average transfer coefficients for plate fin and elliptic tube exchangers, mass transfer experiments were performed using the naphthalene sublimation technique. By means of the heat and mass transfer analogy, the average coefficients of mass transfer can be easily converted to heat transfer results. In accordance with the analogy, the experimental conditions, with naphthalene plates forming the rectangular channel of the exchanger, simulated isothermal fins. Since in practical situations the fins are not isothermal, one can rationalize such a fact by using the concept of fin efficiency, which is a common procedure in heat transfer calculations. The transfer coefficients of the present research were compared with those for circular tube exchangers, found in the pertinent literature, and the comparison revealed no major differences. This is a positive outcome, since the use of elliptic tubes, as it will be shown, reduces substantially the pressure drop in the rectangular channel and increases the fin efficiency improving the transfer characteristics. The mass transfer measurements were performed by weighing the naphthalene pieces before and after a data run characterized by the flow Reynolds number. The Reynolds number range was 150-1300. The present results are directly applicable to air conditioning devices. (C) 2001 Elsevier Science Inc. All rights reserved. [References: 16]
机译:为了确定板翅片和椭圆管交换器的平均传递系数,使用萘升华技术进行了传质实验。通过传热和传质的类比,传质的平均系数可以轻松转换为传热结果。按照类比,在萘板形成交换器矩形通道的实验条件下,模拟了恒温翅片。由于在实际情况中散热片不是等温的,因此可以通过使用散热片效率的概念来合理化这一事实,这是传热计算中的常见程序。将本研究的传输系数与相关文献中发现的圆管交换器的传输系数进行了比较,该比较显示没有重大差异。这是一个积极的结果,因为如将显示的那样,使用椭圆管显着降低了矩形通道中的压降,并提高了翅片效率,从而改善了传输特性。通过在以流动雷诺数为特征的数据运行之前和之后对萘片进行称重来进行传质测量。雷诺数范围是150-1300。目前的结果直接适用于空调设备。 (C)2001 Elsevier Science Inc.保留所有权利。 [参考:16]

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号