首页> 外文期刊>Iron & Steelmaker >Investigation of Transmission System Voltage Flicker Due to Multiple AC and DC Furnace Operation
【24h】

Investigation of Transmission System Voltage Flicker Due to Multiple AC and DC Furnace Operation

机译:交流电和直流电炉多次运行引起的传输系统电压闪变的研究

获取原文
获取原文并翻译 | 示例
           

摘要

The operation of rapidly varying loads, such as AC and DC arc furnaces, in large industrial power systems will cause voltage flicker on the utility system. System planning will help determine the available short circuit duty at the PCC to keep the voltage flicker within acceptable limits. There are a variety of ways to measure voltage flicker, such as perceptible flicker limit curves, the SCVD calculation and on-site field tests. The ultimate determination of whether unacceptable voltage flicker exists in a system will be complaints from customers actually experiencing objectionable or noticeable flicker in industrial or commercial facilities and residential households.
机译:在大型工业电源系统中,快速变化的负载(例如AC和DC电弧炉)的运行会在公用系统上引起电压闪烁。系统规划将帮助确定PCC上可用的短路占空比,以将电压闪烁保持在可接受的范围内。有多种测量电压闪烁的方法,例如可感知的闪烁极限曲线,SCVD计算和现场现场测试。对于系统中是否存在不可接受的电压闪烁的最终确定,将是客户在工业或商业设施以及居民家庭中实际遇到令人反感或明显的闪烁的投诉。