Modelling and Analysis of Switching Overvoltages Caused by Short Circuits in MV Cables Connected with Overhead Lines

机译:架空线与中压电缆短路引起的开关过电压建模与分析

获取原文
获取原文并翻译 | 示例

摘要

In rural power distribution networks, the cause of disturbances is typically weather related, like thunder, snow and ice, and trees fallen by snow, wind and storms [1]. In areas supplied by overhead lines, an auto-reclosure sequence is commonly used to clear temporary faults. In these areas, the share of permanent faults is typically less than 10% [1,2]. In Finland, on average, about 70% of permanent faults in rural MV networks are caused by weather conditions such as thunder, snow, icing, storm, hard wind and fallen trees [1]. However, the cause of the majority of faults remains unknown when they are cleared automatically. Typically, no statistics of the causes of temporary faults is available in literature [3].
机译:在农村配电网中,干扰的原因通常与天气有关,例如雷电,雪和冰以及被雪,风和暴风雨倾倒的树木[1]。在架空线提供的区域中,通常使用自动重合闸顺序来清除临时故障。在这些地区,永久性断层所占比例通常小于10%[1,2]。在芬兰,平均而言,农村中压电网中约70%的永久性断层是由天气状况引起的,例如雷电,降雪,结冰,暴风雨,强风和倒下的树木[1]。但是,大多数故障的原因在自动清除后仍然未知。通常,文献[3]中没有关于临时故障原因的统计信息。