Influence of Measurement Parameters on Frequency Response Analysis Diagnosis of Oil-Immersed Transformer

机译:测量参数对油浸式变压器频率响应分析诊断的影响

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Appropriate monitoring and maintenance become important as an oil-immersed transformer ages. Generally, dissolved gas analysis (DGA) is effective for the online diagnosis, and if an abnormality is detected, frequency response analysis (FRA) is effective for the offline diagnosis to localize the failed part. FRA diagnosis detects a slight change of waveforms; however, external factors may influence the results. Here, we discuss the influence of an insulating oil presence, tap position, and measurement lead wire length as possible parameters that influence the FRA characteristics. We confirmed that the measurement parameters examined here greatly influenced the FRA characteristics. In the actual diagnosis, it is important to remove these external parameters as much as possible, and keep a detailed record of the measurement parameters.
机译:随着油浸式变压器的老化,适当的监视和维护变得很重要。通常,溶解气体分析(DGA)对于在线诊断是有效的,并且如果检测到异常,则频率响应分析(FRA)对于离线诊断对于定位故障部分是有效的。 FRA诊断可检测到波形的轻微变化;但是,外部因素可能会影响结果。在这里,我们讨论绝缘油的存在,抽头位置和测量导线长度的影响,作为可能会影响FRA特性的参数。我们确认,此处检查的测量参数极大地影响了FRA特性。在实际诊断中,重要的是要尽可能多地除去这些外部参数,并详细记录测量参数。