The purpose of this paper is to analyze the correlation relationship between the salt contamination environment and the actual damage to electric power distribution equipment caused by two typhoons, 2012 typhoon No. 4 (T1204) and 2011 typhoon No. 15 (T1115). T1204 caused salt contamination damage to voltage-current transformers (VCTs), while the T1115 caused no damage to VCTs installed in a same target area. In this paper, the salt contamination environment during the two typhoons, which includes the maximum wind speed, the accumulated rainfall, and the Na+ flux, is evaluated by a weather reproduction simulation to discuss the causal relationship between the salt contamination environment and the VCT damage. A damage evaluation model is proposed to evaluate the salt-induced damage risk potential of the VCT for reasonable restoration activity.
机译:本文旨在分析2012年第4号台风(T1204)和2011年第15号台风(T1115)造成的盐污染环境与配电设备实际损坏之间的相关关系。 T1204对电压-电流互感器(VCT)造成盐污染损害,而T1115对安装在同一目标区域的VCT没有造成损害。本文通过天气再现模拟对包括最大风速,累积降雨和Na +通量在内的两个台风期间的盐污染环境进行了评估,以探讨盐污染环境与VCT损害之间的因果关系。 。提出了一种损伤评估模型,以评估盐分对VCT造成的合理恢复活动的潜在损害风险。