摘要

A sudden capacity increase in demand during the summer peak, or in contingencies such as malfunctioning transformers, may cause an overload in normal transformers. In this paper, on the basis of overloaded transformer operation in distribution substations, thermal aging testing in oil was carried out under various overload patterns, such as short-term overload and long-term overload, but with the winding insulation paper's lifespan loss kept constant. From the results, various characteristics, such as the mean degree of polymerization and production of furfural and (CO_2+CO), and their effects on the lifespan loss of the insulation paper, were obtained.
机译:在夏季高峰期,需求突然增加,或者由于变压器故障等意外情况,可能会导致正常变压器过载。本文基于变电站的变压器过载运行,在短期过载和长期过载等多种过载模式下进行了油品的热老化试验,但绕组绝缘纸的寿命损耗保持恒定。从结果获得了各种特性,例如平均聚合度和糠醛和(CO_2 + CO)的产生,以及它们对绝缘纸的寿命损失的影响。