首页> 外文期刊>EC&M >Testing contact quality on live motor starters
【24h】

Testing contact quality on live motor starters

机译:测试带电电动机起动器的接触质量

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

As a maintenance electrician, I'm sure you've been in the high-pressure situation of having to get a "failed" motor running ASAP. And, you probably had to use all the troubleshooting techniques you acquired and mastered over the years. Well here's a tried-and-true technique you can use that involves testing the contact quality on live starters. Sound odd or intriguing? It shouldn't. Remember, your typical 3-phase manual or magnetic motor starter has three sets of power contacts and three overload (OL) relays. When you energize a motor through these types of starters, equal currents theoretically should flow through each contact and OL relay. So, you can measure the voltage drop across each contact or OL relay pole and compare the readings with one another.
机译:作为维护电工,我敢肯定您一直处于高压状态,必须尽快使“故障”电动机运行。而且,您可能不得不使用多年来获得和掌握的所有故障排除技术。好吧,这里是您可以使用的一种久经考验的技术,其中涉及测试带电启动器的接触质量。听起来奇怪还是有趣?不应该这样请记住,典型的三相手动或电磁电动机启动器具有三组电源触点和三个过载(OL)继电器。当您通过这些类型的启动器为电动机通电时,理论上应在每个触点和OL继电器上流过相等的电流。因此,您可以测量每个触点或OL继电器极上的压降,并将读数相互比较。