Heat recovery of air ventilation is a means of energy conversation in buildings. In the present paper, a plastic film heat recovery ventilator that works under cross-flow mode was developed. The thin film vibrates when airflow passes through the channels, which enhances heat exchange performance. Experiments, as well as theoretical analyses, were carried out to study the performance of such a unit. Results show that the effectiveness of the heat exchanger varies from 0.65 to 0.85 with airflow rate and the pressure drop is less than 20.0 Pa. Film vibration induced by airflow can improve heat transfer. The extent of the enhancement is proportional to film vibration intensity that increases with airflow rate while decreases with film thickness.
机译:空气热能回收是建筑物中进行能量交换的一种手段。本文开发了一种在错流模式下工作的塑料薄膜热回收通风机。当气流通过通道时,薄膜会振动,从而增强了热交换性能。进行了实验以及理论分析,以研究这种装置的性能。结果表明,换热器的效率随风量的变化而在0.65至0.85之间变化,压降小于20.0 Pa。气流引起的薄膜振动可以改善热传递。增强程度与薄膜振动强度成正比,薄膜振动强度随气流速率增加而随薄膜厚度减小。