Nucleate boiling heat transfer coefficients of HCFC22, HFC134a, HFC125, and HFC32 on various enhanced tubes

机译:HCFC22,HFC134a,HFC125和HFC32在各种增强管上的核沸腾传热系数

获取原文
获取原文并翻译 | 示例

摘要

In this study, nucleate boiling heat transfer coefficients (HTCs) of HCFC22, HFC134a, HFC125, HFC32 were measured on a low fin, Turbo-B, and Thermoexcel-E tubes. All data were taken at the liquid pool temperature of 7℃ on horizontal tubes of 152 mm length and 18.6-18.8 mm outside diameter at heat fluxes of 10-80 kW m{sup}(-2) with an interval of 10 kW m{sup}(-2) in the decreasing order of heat flux. For a plain and low fin tubes, refrigerants with higher vapor pressures showed higher nucleate boiling HTCs consistently. This was due to the fact that the wall superheat required to activate given size cavities became smaller as pressure increased. For Turbo-B and Thermoexcel-E tubes, HFC125 showed a peculiar behavior exhibiting much reduced HTCs due to its high reduced pressure. The heat transfer enhancement ratios of the low fin, Turbo-B, and Thermoexcel-E tubes were 1.09-1.68, 1.77-5.41, 1.64-8.77 respectively in the range of heat fluxes tested.
机译:在这项研究中,在低翅片,Turbo-B和Thermoexcel-E管上测量了HCFC22,HFC134a,HFC125,HFC32的核沸腾传热系数(HTC)。所有数据均在长度为152 mm,外径为18.6-18.8 mm的水平管上,在7℃的液池温度下,热通量为10-80 kW m {sup}(-2),间隔为10 kW m { sup}(-2)按热通量的降序排列。对于平翅片和低翅片管,具有较高蒸气压的制冷剂始终显示出较高的成核沸腾HTC。这是由于以下事实:随着压力的增加,激活给定尺寸的腔所需的壁过热变得较小。对于Turbo-B和Thermoexcel-E管,HFC125表现出独特的行为,由于其高减压特性,HTC大大减少。在测试的热通量范围内,低翅片管,Turbo-B管和Thermoexcel-E管的传热增强比分别为1.09-1.68、1.77-5.41、1.64-8.77。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号