Experimental performance study of a small wall room air conditioner retrofitted with R290 and R1270

机译:装有R290和R1270的小型壁挂式房间空调的实验性能研究

获取原文
获取原文并翻译 | 示例
           

摘要

An original R22 wall room air conditioner with a cooling capacity of 2.4 kW and energy efficiency ratio (EER) of 3.2 is retrofitted with a compressor of a 20% larger displacement to charge R290 and R1270 for performance experiments. The results show that for R1270, only adopting a same kind mineral lubricant of higher viscosity would supply 2.4% higher cooling capacity and 0.8% higher EER than those of the original R22 system under normal condition, and for R290, adopting the larger displacement compressor simultaneously would also obtain better performance. Alternative systems all have higher increase rate and greater increment in both cooling capacity and EER than the original R22 system when outdoor temperature decreases. The R1270 system has great increase in cooling capacity and negligible decrease in EER. Refrigerant charge distribution is also investigated and it indicates that the charge within both heat exchangers and compressor ought to be reduced.
机译:原来的R22壁挂式房间空调器的制冷量为2.4 kW,能效比(EER)为3.2,其压缩机的排量增加了20%,以便为R290和R1270进行性能实验。结果表明,对于R1270,在正常条件下,仅使用相同粘度的同类矿物润滑剂将提供比原始R22系统高2.4%的冷却能力和0.8%的EER;对于R290,同时采用大排量压缩机也会获得更好的性能。当室外温度降低时,替代系统都比原始R22系统具有更高的增长率和更大的制冷量和EER。 R1270系统的制冷量大大增加,而EER的减少可忽略不计。还研究了制冷剂的进料分布,这表明应该减少热交换器和压缩机内的进料。