首页> 外文期刊>International Journal of Refrigeration >An implicit curve-fitting method for fast calculation of thermal properties of pure and mixed refrigerants
【24h】

An implicit curve-fitting method for fast calculation of thermal properties of pure and mixed refrigerants

机译:一种隐式曲线拟合方法,用于快速计算纯制冷剂和混合制冷剂的热性能

获取原文
获取原文并翻译 | 示例
           

摘要

Calculations of refrigerant thermal properties are desired to be very fast and stable in cases of simulation of refrigeration system, etc. The traditional method based on equation of state cannot meet such requirement because of unavoidable iterations in calculation. In this paper, a new calculation method for refrigerant thermal properties is presented, Low order implicit polynomial equations are got by using curve-fitting method at first, and then explicit formulae for calculating refrigerant thermal properties quickly are obtained by getting the analytical solution of these implicit equations. Explicit fast calculation formulae for thermal properties of R22 and R407C, covering the saturated temperature of - 60~80 ℃ and superheat of 0-65 ℃, are presented as examples. The calculation speeds of the formulae of R22 are about 140 times faster than those of REFPROP 6.01 while the formulae of R407C are about 1000 times faster; The total mean relative deviations of the fast calculation formulae for R22 and R407C are less than 0.02%.
机译:在制冷系统的仿真等情况下,期望制冷剂的热特性的计算非常快速和稳定。基于状态方程的传统方法由于计算中不可避免的迭代而不能满足这种要求。本文提出了一种新的制冷剂热特性计算方法,首先采用曲线拟合的方法得到了低阶隐式多项式方程式,然后通过求解得到它们的解析解,快速求出了计算制冷剂热特性的明确公式。隐式方程。给出了R22和R407C热性能的显式快速计算公式,包括-60〜80℃的饱和温度和0-65℃的过热度。 R22公式的计算速度大约是REFPROP 6.01的140倍,而R407C公式的计算速度大约是REFPROP 6.01的1000倍。 R22和R407C的快速计算公式的总平均相对偏差小于0.02%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有