In this study, an improved cooling cycle for a conventional multi-evaporators simple compression system utilizing ejector for vapour precompression is analyzed. The ejector-enhanced refrigeration cycle consists of multi-evaporators that operate at different pressure and temperature levels. A one-dimensional mathematical model of the ejector was developed using the equations governing the flow and thermodynamics based on the constant-area ejector flow model. The model includes effects of friction at the constant-area mixing chamber. The energy efficiency and the performance characteristics of the novel cycle are theoretically investigated. The comparison between the novel and conventional system was made under the same operating conditions. Also, a comparison of the system performances with environment friendly refrigerants (R290, R600a, R717, R134a, R152a, and R141b) is made. The theoretical results show that the COP of the novel cycle is better than the conventional system.
机译:在这项研究中,分析了利用喷射器进行蒸汽预压缩的传统多蒸发器简单压缩系统的改进冷却循环。喷射器增强型制冷循环由在不同压力和温度水平下运行的多蒸发器组成。使用基于恒定面积喷射器流动模型的控制流动和热力学的方程,开发了喷射器的一维数学模型。该模型包括恒定面积混合室的摩擦力影响。理论上研究了新型循环的能量效率和性能特征。在相同的操作条件下对新型系统和常规系统进行了比较。此外,还对系统性能与环境友好型制冷剂(R290,R600a,R717,R134a,R152a和R141b)进行了比较。理论结果表明,新型循环的COP优于常规系统。