Water and swab samples were collected from 13 hospitals and analyzed for Legionella counts. Legionella was detected in eight out of 13 hospitals and in 22 of 130 water and swab-collected samples. A total of 72.7% of the strains were L. pneumophila ser. 1, 22.7% were L. pneumophila ser. 2-14, and 4.5% did not belong to any of these groups. AFLP typing of the L. pneumophila ser. 1 strains generated two distinguishable AFLP types. There was no significant correlation to the sample type with Legionella recovery. Legionella isolation was more likely to occur in the cooling towers than the water system. Water temperatures of 30-40°C seem to favor Legionella growth. Of the 265 serum samples taken from the medical and technical staff for the control of IgG titre, 89.4% were negative, 7.2% were positive, and for 3.4% the result was doubtful. No association between IgG titre and maximum observed level of Legionella occurrence was detected.
机译:从13家医院收集了水和棉签样本,并对军团菌计数进行了分析。在13所医院中的8所医院和130份水和棉签收集的样本中,有22份发现了军团菌。总共72.7%的菌株是嗜肺乳杆菌。 1,22.7%为肺炎乳杆菌。 2-14岁,其中4.5%不属于这些人群。嗜肺乳杆菌序列的AFLP分型。 1个菌株产生了两种可区分的AFLP类型。军团菌的回收率与样品类型无显着相关性。与水系统相比,冷却塔中更容易发生军团菌隔离。 30-40°C的水温似乎有利于军团菌的生长。从医务人员那里获得的265份血清样本用于控制IgG滴度,其中89.4%阴性,7.2%阳性,3.4%的结果令人怀疑。未检测到IgG滴度和军团菌最大观察水平之间的关联。