AbstractTwenty‐six absorbent—refrigerant combinations, holding good promise as fluid systems, have been considered for single stage absorption air conditioning system. These fluids have been compared on the basis of solution characteristics, life expectancy characteristics and refrigeration cycle characteristics. The mass flow rates of rich and poor solutions per ton of refrigeration capacity and the coefficient of performance (CP) were compared for an evaporator temperature of 5°C, absorber and condenser temperatures of 35°C and a generator temperature of 120°C (low grade energy sources). More than half of the waste energy available in industry happens to be at a temperatures below 200°C. Other types of low grade thermal energy such as solar energy and geothermal energy can be used in operating vapour absorption refrigeration and air‐conditionin
展开▼