Partial discharges are well known as a source for insulation degradation in power transformers. A hybrid transformer model is introduced to simulate the transformer winding transient response. Transformer structural data is used to determine the hybrid model parameters. Calculations of the hybrid transient model parameters are based on the parameters of the lumped parameter equivalent transformer model and electromagnetic rules. Modern computation techniques and optimizations are employed beside this model for PD location using the multi conductor transmission line model and also to analyze its propagation aimed at achieving (i) more reliable simulation results (ii) less computational time (iii) accurate results for a wide range of frequency. The simulation results on a 66 kV, 25 MVA fully interleaved winding are presented. The measurement results on this winding are employed to validate this model.