Passivation of Grid-Following VSCs: A Comparison Between Active Damping and Multi-Sampled PWM

机译:Passivation of Grid-Following VSCs: A Comparison Between Active Damping and Multi-Sampled PWM

获取原文
获取原文并翻译 | 示例
       

摘要

This article compares different strategies used to enhance the stability properties of grid-following voltage-source converters (VSCs). Because of digital delays, VSC admittance exhibits a nonpassive zone, which introduces negative damping and may destabilize the grid-connected operation. It is shown that typically used active damping (AD) strategies only bring positive impact up to a certain frequency, while deteriorating admittance properties around and above the Nyquist frequency. Multi-sampled pulsewidth modulation (MS-PWM) greatly extends the passive admittance region, using only a single-loop current controller. Experimental admittance measurements are performed on a single-phase VSC, up to twice the switching frequency. Subsequently, different grid-connected scenarios are tested to show that MS-PWM retains stable operation, where AD methods cause instability. This article also offers analytic modeling and experimental measurements of noise propagation for compared strategies. It is shown that derivative-based AD is not highly sensitive; however, MS-PWM offers additional noise suppression.