首页> 外文期刊>Archives of Electrical Engineering >Investigation of GIC effects on core losses in single phase power transformers
【24h】

Investigation of GIC effects on core losses in single phase power transformers

机译:GIC对单相电力变压器铁心损耗的影响研究

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a method for estimation of core losses in banks of single phase power transformers that are subjected to an injected DC current such as geomagnetically induced currents (GIC).The main procedure of the core loss calculation is to obtain a magnetic flux density waveform in both time and location by using a novel algorithm based on 3D FEM inside the core and then to calculate the loss distribution based on loss separation theory. Also, a simple and effective method is proposed for estimation of losses of asymmetric minor loops by using combination of symmetric loops. The effect of DC biasing on core losses in single phase power transformers is investigated and the sensitivity of core type and material is evaluated, the results shows that DC current biasing could increase core losses up to 40 percent or even more.
机译:本文提出了一种评估单相电力变压器组中铁心损耗的方法,这些单相电力互感器要承受注入的直流电流(例如地磁感应电流(GIC))。铁心损耗计算的主要过程是获得磁通量密度波形通过使用基于内核内部3D FEM的新颖算法在时间和位置上进行定位,然后基于损耗分离理论计算损耗分布。此外,提出了一种简单有效的方法,通过使用对称回路的组合来估计不对称次回路的损耗。研究了直流偏置对单相电力变压器铁心损耗的影响,并评估了铁心类型和材料的灵敏度,结果表明,直流电流偏置可以使铁心损耗增加多达40%甚至更多。