首页> 外文期刊>Archives of Civil and Mechanical Engineering >Summer overheating of a passive sports hall building
【24h】

Summer overheating of a passive sports hall building

机译:夏季被动式体育馆建筑过热

获取原文
获取原文并翻译 | 示例
           

摘要

Reported measurements were intended as a preliminary check of a free run of a sports hall passive building in summer conditions. Indoor microclimate measurements lasted for three hot summer days and were carried out at the time when there was no building occupancy. In adverse conditions of high ambient air temperature and switched off ventilation acute overheating was observed. Night cooling, easily available measure of overheating protection was not applied, so there was no chance for discharge of high internal capacity of this building. A specific mode of building management had a critical impact on its internal microclimate and would raise user dissatisfaction. In close perspective of widespread implementation of near zero energy building standard, often reported overheating problem becomes an important issue. It was also shown that thermal comfort measurements maybe unexpectedly and substantially affected by window location and solar radiation geometry. (C) 2015 Politechnika Wroclawska. Published by Elsevier Sp. z o.o. All rights reserved.
机译:报告的测量结果旨在初步检查运动场馆被动式建筑物在夏季的状况。室内微气候测量持续了三个炎热的夏天,并在没有建筑物居住的时候进行。在高环境空气温度和关闭通风的不利条件下,观察到严重的过热现象。没有采用夜间冷却,没有采用容易获得的过热保护措施,因此没有机会释放该建筑物的高内部容量。特定的建筑管理模式对其内部的微气候具有至关重要的影响,并且会引起用户的不满。在广泛实施接近零能耗的建筑标准的紧密视角下,经常报告的过热问题已成为一个重要问题。还表明,窗户的位置和太阳辐射的几何形状可能会意外地并极大地影响热舒适度的测量。 (C)2015 Politechnika弗罗茨瓦夫。由Elsevier Sp。发行。动物园。版权所有。