In this paper, the experimental investigation was carried out for the performance of adjustable ejector used in a multi-evaporator refrigeration system. The adjustable ejector with a spindle to adjust the area of nozzle throat was applied to deal with the considerable variation in primary cooling load for air-conditioning in such system. The adaptability of the adjustable ejector for the system was first evaluated by the tests and the results show the adjustable ejector can efficiently deal the problem of variable primary cooling load in the system. The tests for the performance of pressure recovery were subsequently carried out. The experimental results indicate that the Pressure Recovery Ratio (PRR) and Relative Pressure Recovery Ratio (RPRR) can reach 20% and 8%, respectively, in the system with design operating condition, which means the adjustable ejector applied in multi-evaporator refrigeration system may be a promising approach for a practical multi-evaporator refrigeration system with significant energy saving. It also can be found that PRR and RPRR are reduced with decreasing of the primary cooling load.
机译:在本文中,对用于多蒸发器制冷系统的可调喷射器的性能进行了实验研究。使用带有主轴以调节喷嘴喉部面积的可调节喷射器来应对这种系统中空调的一次冷却负荷的显着变化。首先通过测试评估了可调式喷射器对系统的适应性,结果表明,可调式喷射器可以有效地解决系统中主冷却负荷可变的问题。随后进行了压力恢复性能的测试。实验结果表明,在设计工况条件下,系统的压力恢复率(PRR)和相对压力恢复率(RPRR)分别达到20%和8%,这意味着可调喷射器在多蒸发器制冷系统中的应用。对于实用的多蒸发器制冷系统而言,这可能是一种有前途的方法,具有显着的节能效果。还可以发现,随着主冷却负荷的降低,PRR和RPRR降低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号