首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >A complete model of wet cooling towers with fouling in fills
【24h】

A complete model of wet cooling towers with fouling in fills

机译:充满污垢的湿式冷却塔的完整模型

获取原文
获取原文并翻译 | 示例
           

摘要

A cooling tower basically consists of three zones; namely, spray zone, packing and rain zones. In cooling towers, a significant portion of the total heat rejected may occur in the spray and rain zones. These zones are modeled and solved simultaneously using engineering equation solver (EES) software. The developed models of these zones are validated against experimental data. For the case study under consideration, the error in calculation of the tower volume is 6.5% when the spray and rain zones are neglected. This error is reduced to 3.15% and 2.65% as the spray and rain zones are incorporated in the model, respectively. Furthermore, fouling in cooling tower fills as well as its modeling strategy is explained and incorporated in the cooling tower model to study performance evaluation problems. The fouling model is presented in terms of normalized fill performance index (eta(F.norm)) as a function of weight gain due to fouling. It is demonstrated that the model is asymptotic, which is similar to typical asymptotic fouling model used in conventional heat exchangers. (c) 2006 Elsevier Ltd. All rights reserved.
机译:冷却塔基本上由三个区域组成;即喷雾区,填料区和雨区。在冷却塔中,排出的总热量的很大一部分可能发生在喷雾区和雨水区。使用工程方程求解器(EES)软件对这些区域进行建模和求解。这些区域的开发模型已针对实验数据进行了验证。对于正在考虑的案例研究,当忽略喷雾和雨水区时,塔体积的计算误差为6.5%。由于该模型分别包含了喷雾区和雨区,因此该误差分别降低到3.15%和2.65%。此外,对冷却塔填料的结垢及其建模策略进行了解释,并将其纳入冷却塔模型中以研究性能评估问题。结垢模型是根据归一化填充性能指数(eta(F.norm))表示的,该指标是结垢引起的重量增加的函数。证明了该模型是渐近的,类似于常规热交换器中使用的典型渐近结垢模型。 (c)2006 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号