This paper presents the results of an experimental analysis which compares in terms of energetic performances the refrigeration capacity control obtained by means of a variable-speed compressor with the on/off control deriving from a classical thermostatic device. The compressor considered is semi-hermetic reciprocating and is a component of a vapour compression refrigeration plant subjected to a commercially available cold store. The compressor working with the fluids R22, R507 and R407C and designed for a revolution speed corresponding to the compressor supply current nominal frequency of 50 Hz, has been tested varying the frequency in the range 30-50 Hz. In this range, the most suitable working fluids proposed as substitutes of the R22 as the R407 C(R32/R125/R134a 23/25/52% in mass), the R507 (R125/R413A 50/50% in mass) and the R417A (R125/R134a/R600 46.6/50/3.4% in mass) have been tested. The results show that, using the R407C, it is possible an average an electric energy consumption about 12% smaller when an inverter is employed to control the compressor refrigeration capacity instead of the thermostatic control which imposes on/off cycles on the compressor, working at the nominal frequency of 50 Hz. So the R407C confirms its superiority in comparison with the R417A and R507; only the R22 shows a better performance.
机译:本文介绍了一项实验分析的结果,该实验分析在能量性能方面比较了通过变速压缩机获得的制冷量控制与从经典恒温装置获得的开/关控制。所考虑的压缩机是半密封往复式的,并且是经受商业可得的冷库的蒸汽压缩制冷设备的组成部分。已经测试了使用流体R22,R507和R407C并设计为对应于50 Hz压缩机电源电流额定频率的转速的压缩机,并在30-50 Hz范围内改变了频率。在此范围内,建议使用最合适的工作液替代R22,例如R407 C(R32 / R125 / R134a质量为23/25/52%),R507(R125 / R413A质量为50/50%)和已测试R417A(R125 / R134a / R600质量为46.6 / 50 / 3.4%)。结果表明,使用R407C,当采用逆变器控制压缩机的制冷能力而不是对压缩机施加开/关循环的恒温控制时,使用R407C可以平均减少约12%的电能消耗。 50 Hz的标称频率。因此,R407C证实了其与R417A和R507相比的优越性。只有R22表现出更好的性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号