首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Experimental research of the guiding channels effect on the thermal performance of wet cooling towers subjected to crosswinds - Air guiding effect on cooling tower
【24h】

Experimental research of the guiding channels effect on the thermal performance of wet cooling towers subjected to crosswinds - Air guiding effect on cooling tower

机译:导风道对侧风湿式冷却塔热力性能影响的实验研究-冷却塔的导风效果

获取原文
获取原文并翻译 | 示例
           

摘要

The thermal performance of a natural-draft wet cooling tower model with inlet airflow guiding channels under crosswinds conditions was monitored and experimented. Three patterns of the air guiding channels with different setting angles (including 60°, 70° and 80°) were tested under various crosswinds velocities. The results show that the air flow rate and the cooling efficiency increase remarkably after the inlet air is directed. On the basis of testing data, some thermal performance parameters including the Lewis factor, the heat and mass transfer coefficient were also calculated and analysed. The results indicate that the Lewis factor ranges from 0.95 to 1.15, which is in accordance with the data of other literatures. Besides, it is found that the optimum setting angle for the air guiding channels is 70°, and it does not change with the channel quantity which ranges from 18 to 88. However, it should be noticed that although the guiding channels with 70° setting angle lead to better cooling performance, they may cause more circulating water consumption.
机译:监测并试验了自然风湿式冷却塔模型在侧风条件下具有进气流引导通道的热性能。在不同的侧风速度下,测试了具有不同设定角(包括60°,70°和80°)的三种导风通道模式。结果表明,引导进气后,空气流量和冷却效率显着提高。在测试数据的基础上,还计算并分析了一些热性能参数,包括路易斯因子,传热和传质系数。结果表明,路易斯因子在0.95至1.15的范围内,这与其他文献的数据一致。此外,发现导风通道的最佳设置角度为70°,并且不会随通道数量的变化而变化,通道数量在18到88之间。但是,应该注意的是,尽管导风通道的设置角度为70°角度导致更好的冷却性能,它们可能会导致更多的循环水消耗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号