首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Influence of non-uniform layout fillings on thermal performance for wet cooling tower
【24h】

Influence of non-uniform layout fillings on thermal performance for wet cooling tower

机译:布局不均匀填充对湿式冷却塔热力性能的影响

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Based on the similarity theory, thermal-state model experiment in lab is performed to investigate the thermal performance of wet cooling towers under different layout patterns of fillings, and five kinds of layout patterns, including uniform layout and four kinds of non-uniform layout patterns, are studied in this paper. Experimental results manifest that the thermal performance of wet cooling towers under nonuniform layout patterns is outstanding by calculating and analyzing five performance parameters, which are ooling termperature difference, cooling efficiency, Merkel number, Lewis number and the ratio of evaporative heat rejection. Additionally, research also obtained the optimal three-block layout pattern of fillings in which the radius ratio of r(a)/r(c) is approximately 0.44 and r(b)/r(c) is around 0.71; here r(a), r(b) and r(c) are the radius of three blocks, respectively. What's more, compared with the uniform layout pattern of fillings, the thermal performance of the optimal layout pattern can enhance by 30% at maximum within the scope of this test. (C) 2015 Elsevier Ltd. All rights reserved.
机译:基于相似理论,在实验室进行了热态模型实验,研究了湿冷却塔在不同填充物布局模式下的热性能,并研究了五种布局模式,包括均匀布局和四种非均匀布局模式。本文进行了研究。实验结果表明,湿式冷却塔在非均匀布局模式下的热性能是通过计算和分析五个性能参数而得到的,这些性能参数是冷却温度差,冷却效率,默克尔数,路易斯数和蒸发散热率。此外,研究还获得了最优的三块式布局填充物,其中r(a)/ r(c)的半径比约为0.44,r(b)/ r(c)的半径比约为0.71;在此,r(a),r(b)和r(c)分别是三个块的半径。而且,与填充物的均匀布局模式相比,在此测试范围内,最佳布局模式的热性能最多可以提高30%。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号